goldbrick said:
NEC Article 240.4

(D)
Thanks, the famous 'small conductor rule.'

This is why Learjet was able to provide a correct and succinct answer.
So to answer my earlier question about FMC -- No, because 240.4.(D) would still apply
 
Unless the wire is 8AWG or larger. Then THWN in conduit can use the 75C table.

I think another 'gotcha' is that any terminals that fit the smaller wires are rarely rated for 75C as well.
 